Sunday, January 19, 2014

10. Wiring and Safety Components for PV Solar Systems

Main Subjects
  • Type of cables and Characteristics used in Solar PV Systems.
  • Selection of Conduit
  • Disconnect Switches
  • Selection of Fuse/ Circuit Breaker
  • Ground Fault Protection
  • Labeling Requirements
Type of cables and Characteristics used in Solar PV Systems.
  1. Underground Service Entrance Cable - for outdoor applications. not designed for fire ratings.
  2. External Wiring - 
  3. Building Wiring (Internal Applications) - THHN, THWN - Heat Resistant Thermoplastic - doent run outside building. No sunlight resistant Characteristics. 
  4. Battery wiring - Moister Resistant Thermoset (EHW) Heat Resistant themoplastic, Flexible wiring is another choice, make sure terminals and legs are designed for battery use.
  5. Grounding Wiring - Bare copper or Insulated copper conductor.
Selection of Conduit

  • Selection - Depends up on the location (dry/wet)
  • Temperature of Installation.


  • Flexible and Rigid
  • Metallic Conduit
  • Non-Metallic Conduit

EMT(Electric Metallic Conduit) used for long run, less expensive, inside & outside application

FMT(Flexible Metallic conduit) Used for indoor application, for shot run ,more cost, less labor.

Non-Mettalic conduit - Rigid PVC, - Used for underground / Outside building.

Disconnect Switches
As per Utility requirements, PV Circuit and Inverter output should be lockable disconnect switch.

One Lockable Disconnect switch should be near the meter and should be visible and utility can access 24/7 .
will be operated by utility service person.

Selection of Fuse/ Circuit Breaker
For High Voltage DC Applications, the Fuse should be Selected accordingly.
Case Study:-

Ground Fault Protection
Is a standard in Grid Tied inverter.
Refer
solarprofessional.com

Labeling Requirements
DC Disconnect.
Utility Power Interconnection Point.
Building Exterior - Should have details of PV Source and all disconnection of the system.

========================================================================
CASE STUDY -1
========================================================================


Cable - A
Reference 690.8A, 690.8B --> Connect from PV Module.

(No of modules (strings) wired in parallel)  X  (Short circuit current-Isc) X  1.25 (safety factor for irradiance)  X  1.25(Cable safety factor)

Cable shall not carry 80% of Max.
Where the maximum Current is expected to continue for 3 Hours or more, considered as continuous load (NEC Code article 100)

Total Safety factor - 1.25x1.25 = 1.56
Isc - 5.5A

Cable Selection for PV - 1.56 X 5.5A = 8.6Amp


Cable - B
Max. Output Current X 1.25 =

Saturday, August 27, 2011

9. Inverter AC from DC

Type of Inverter

A. Utility-Interactive Inverter
   1. Direct Grid
   2. Battery Based
B. Stand-alone Inverter

(A.1)  Grid Direct Inverter
  • No storage
  • High over all Efficiency
  • Works in parallel with the system
Point-1 -->  All grid tied inverters works between 150- 600Volt

Point-2 -->  600Volt is the maximum voltage as per code

Point-3 -->  Will monitor the voltage and frequency of the utility power for Anti-Islanding safety features

Point-4 -->  If low frequency or low voltage will be detected in the grid, the inverter will be automatically                            disconnected from grid power with Anti-Islanding features

Point-5 -->  If the voltage and frequency retains in the grid, the inverter will restart again after monitoring five minutes

  • If any brownout will come, the invertor may shut down.
  • If the voltage drop happens, the inverter may shut down.


GFP - Ground Fault protection in the system.
Will protect from fire 
GFCI - Ground fault circuit interrupter - used for human protections.

Multiplicity - inverter with more than one MPPT.


Technologies in Inverter - Transformer
  1. Large transformer and Low frequency Technology.
  2. Small transformer and High frequency Technology.
  3. Transformer less Technology.
Large transformer and Low frequency Technology.

  • Take High DC voltage from PV array
  • covert DC to AC voltage.


The frequency of the switches operates will be relatively low comparing to other systems.

* Robust System.
* Less number of components.
! Large transformer, too heavy
! Less Efficiency, due to transformer loss.

Small transformer and High frequency Technology.

  • Technology similar to hgh voltage Technology
  • Swiching more faster, smaller light wt. transformer will be used.
  • Few manufacturers with multiple invertor.
Eg. Three invertors in a single system, will operate only one, if the power load is less. the power increases the second invertor will be switched on.

Transformer Less Technology.


AC converts to DC with electronic components 
Referred as ungrounded Invertor.
Only equipment grounding requires, only for shock hazards.

Pros
High Efficieny

Less Wt.
Cons

Additional regulation as per NEC.


Battery Based Inverter
    When Utility is working.
    1. PV Array starts producing power and sends it to battery banks.
    2. When Battery bank is full, power will send to inverter. (from PV)
    3. Inverter Pass the power to Load Center
    4. If PV Solar produces more power, then it passes to the utility grid, and the meter runs.
    5. If the PV array slows down, the load center will consume power from the utility grid.
    If Utility is down.
    1. Automatically, the isolator will disconnects from grid power (Anti-Islanding feature) and monitor the voltage and frequency of the grid power.
    2. Draw power from battery bank to backup the load center, until battery bank become empty. 
    3. Battery bank may charge directly from Utility also.
    Stand Alone Inverter
    1. Take DC Power from Battery bank, turns to AC power.
    2. If Battery power is empty or less than 80%, the alert can turn on the generator/ change over switch.
    3. Feature - Low battery alert 
    4. No ground fault protection needed.
    Sizes of Battery based inverter
    1. Starts from 100W to 6kW.
    2. Can connects in field.
    3. Low frequency transformer technology.
    4. Max input voltage is 48VDC.
    Selecting an Inverter

    DC Voltage window --> Input voltage range DC voltage from PV array - typical is 250VDC - 600VDC

    AC Power Output Value --> Related to PV array input value 15% to 25% extra.

    PV  ---->  Inverter (3000W)

    3000 x 115% = 3450W
    3000 x 125% = 3750W

    Right specification for the project -->
    Disconnect input with inverter -->

    As per NEC code, disconnect/ Isolator should be near to inverter.
    Monitoring facility - Based on customer needs.

    Battery Based Inverter
    Select the AC power source.
    Surge rating of the inverter for motor loads.

    Friday, August 26, 2011

    11. Sizing of Grid Direct PV Solar System

    1. Evaluating the Budget

    2. Evaluating the Space required for Installation

    3.  Estimate the Site Annual energy production

    4.  Sizing the array and Selection of array
    4.a Determine annual Energy consumption

    5.  Looking contract options

    6. Getting ready to match the inverter to an array

    6a.  Power value to inverter of PV
    6b. DC Voltage value to inverter of PV
    6c. AC Voltage value to inverter of PV
    6d  Temperature coefficient of the module

    7. Inverter Maximum current input



    1. Evaluating the Budget

    The Budget of the system whould be estimated based on kW, Area of installation, Technology etc

    2. Evaluating the Space required for Installation

    Space required for the installation will be evaluated based on few factors.

    A. Area:-
    1. Conduct site survey for available space for installation of modules
    2. Consider site clearance for safety of installation and future maintenance and clearance from other services.
               Make sure you have considered dead spaces (the space around the panel)
    3. Run shade analysis for the space.
    4. The Power Density of the module will be quick way to analyse the area, power relation.
    5. Finalize the type of installation
     
    B. Location (Based on Step-3):-

    3.  Estimate the Site Annual energy production

    Step-1   Evaluate the agreement with the utility
    tep-2   Estimate the annual energy production based on modeling programs like PV-Syst
    Step-3   For quick analysis, use PV Watts to measure the energy production
    Step-4   Finalize Tilt, orientation and shading effects of the array
    Step-5   Don't treat this as a promised value



    4.  Sizing the array and Selection of array

    4 A 
    • Collect the utility Bill for 12 months
    • Make a load analysis chart
    • Make sure there is no addition or deletion of load in the system


    5.  Looking contract options     
         Net Metering Agreement:-
    • Extra Energy produced by the client may not be en cashed
    • The client will produce energy and will back up his loads, if any extra energy required, that will be taken from the utility
     True-up period
      The time at which Extra energy produced by PV uploaded to utility
     TOU - (Time of use Metering Method)
       Utility charges the client based on the time of the day he consumes or produces. usually the day time energy cost may be high comparing to night time, hence its advisable to reduce the consumption and increase the power uploading
    FIT (Feed in Thariff Method)
     Energy produced will be connected will be through separate meter and will be considered as a separate entity. Hence the load details will not have any relation between the PV sizing.


    Working Steps:- 
    •    Calculate the energy consumption of client (from step4)
    •    If client may need 5000kWh/Yearly
    •    If Solar PV produces 2000kWh/Yearly
    •    Remaining power can be loaded from utility
    •    Also cross check the maximum demand


    6. Getting ready to match the inverter to an array

       Matching the PV with inverter will be subdivided to three steps

    Power --> Voltage --> Current

    The Calculation should be submitted to electrical inspector if necessary


    6a.  Power value to inverter of PV

    • Options of using multiple inverter should be considered
    • The array output losses to be considered (temp cof, resistivity of the cable, efficiency of the system,)
    • Industrial standard for Eff. is 80% for array
                 5000W array x 80% Eff. = 4000W (Min Inverter rating)
    • Maximum rated power input of the inverter be taken from the spec sheet of the inverter
    • If you connect more number of PV modules to inverter, inverter may not take that power
    • If inverter handle more power for a long run, the life of the inverter may come down
    My recommendation of PV eff.          
                5000W array x 87% Eff. = 4350W ( Inverter rating) next available size is 4.5kW inverter


    Advantage of selecting next higher rating inverter
    • If in a sunny day the irradiance is more than 1000W, the array produce more energy and we may not utilize that power, if the next size selected, we can utilize this additional power.
    • The life span of the inverter will increase, (its not fully loaded)
    • Also check the efficiency of the inverter at different loading (like losses @ 25%, 50% & 75% Loading.
    6b. DC Voltage value to inverter of PV
    Voltage window - Minimum and maximum values of the voltage in the incoming and outgoing side of the inverter
    • Make sure that the array designed for the voltage within the window of the inverter voltage
    • If the input voltage is higher, the inverter will trip
    • If the input voltage is lower, the inverter will shut down
    • Make sure the protection for the DC input side of the inverter
    • Maximum DC voltage willl be recorded by the inverter, if inverter  fails due to high input DC vge, the warranty may not be applicable for the inverter.
    6c. AC Voltage value to inverter of PV
    Check the line voltage
    Match it with inverter output voltage
      Eg: - If the grid voltage is 120/240V we cannot select an inverter is with 210/208V
     


    6d  Temperature coefficient of the module
    The Voltage and temperate of the module will have inverse characteristic, make sure , array voltage will not exceed the inverter's input value
    Temperature coff. of crystalline module is 0.35%/'C (for general calculation)
    Temperature coff. of thin filim module will be crosschecked in technical spec.
    The temperature coff. value of the inverter will always depends on the  type of module.

    Calculate Module's Maximum Voltage

    How to calculate the change in voltage due to temp in a PV Module
    1. Collect the temperature coefficient of the PV module
    2. Collect the record cold temperature for client location in degree celsius 
    3. calculate how many degree Celsius less than STC (25'C) in the site on the record cold day
    4. multiply the temperature coefficient  of he module by the number of degree calculated in step-3
    5. add the value with Voc of the module STC
    Ex:-1
    Voc- 45V
    Temp Coefficient  (+-0.35"C)
    Step-(1)  temp coff  (-0.35"C)
    Step-(2)  record cold temperature for client location in degree Celsius 15"C
    Step-(3)  15'C - 25"C = -10"C
    Step-(4)  -10 x 0.35% = 3.5% rise in voltage (of -ve value fall in voltage, +ve rise in voltage)
    Step -(5) add the value with Voc of the module STC

    Voc- 45V
    Temp Coefficient  (-0.158V/"C)
    Step-(1)  temp coff  (-0.158V/"C)
    Step-(2)  record cold temperature for client location in degree Celsius 15"C
    Step-(3)  15'C - 25"C = -10"C
    Step-(4)  -10 x -0.158V/"C = +1.58Volt rise in voltage (of -ve value fall in voltage, +ve rise in voltage)
    Step -(5) add the value with Voc of the module STC

    Case Study
                    Voc - 45V

    Temp Coefficient  (-0.158V/"C)
    Step-(1)  temp coff  (-0.158V/"C)
    Step-(2)  record cold temperature for client location in degree Celsius -5"C
    Step-(3)  -5'C - 25"C = -30"C
    Step-(4)  -30 x -0.158V/"C = +4.7Volt rise in voltage (of -ve value fall in voltage, +ve rise in voltage)
    Step -(5) add the value with Voc of the module STC  --> 45V + 4.7V = 49.7V



    Taking the vaule from NEC
    The Temperature coff can be taken from the NEC table 690.7
    Execptions-
    When the information provided by manufacturer, you shall calculate the new voltage.
    The table is applicable for only crystalline, (if you are using thin film , this table may not be applicable)
    NEC values are more conservative, that may not work in the system.


    Calculate Module's Minimum Voltage
    The Voltage may go down if the temperature of the stalled will be higher than STC
    If the voltage come down below the window, the inverter may shut down

    Long Term performance of the system

    Over the course of 25 years, the power produced by the PV module may decrease by 1% in every year.
    This factor should consider while we calculating the DC voltage and selection of inverter

    Calculating Minimum DC Voltage in PV module
    Step-1   Collect the temp coff. of PV module in Volt/'C
              This value can be taken from Spec sheet
    Step-2   Collect 2% design temp for your client location i "C
             From ASHRAE 
    Step-3   Determine how may "C to add to (2) based on type of mounting array
    Step-4   Add (3) + (2)
    Step-5   (4) - STC =(5)
    Step-6   (5) x Temp Coefficient = (6)
    Step-7   (6) + Vmp @ STC  = (7)

    Case Study
    Vmp - 37.2

    Step-1   Temp coff. of PV module in Volt/'C    ->    -0.5%/"C
                            37"C x -0.5%/"C = 37"C x -0.005V%/"C = -0.186Volt / "C
              This value can be taken from Spec sheet
    Step-2   2% design ambient temp for your client location -->  33"C

    Step-3   Determine how may "C to add to (2) based on type of mounting array
                  Panel mounted within 6' from ground hence consider --> 35"C
    Step-4   Add (3) + (2)   --> 35"C  +  33"C = 68"C
    Step-5   (4) - STC =(5)   --> 68"C - 25"C  = 43"C
    Step-6   (5) x Temp Coefficient = (6)   --> 43"C x 0.186Volt / "C = -8Volt
    Step-7   (6) + Vmp @ STC  = (7)  --> 37.2Volt + (-8Volt) = 29.2Volt


    Minimum No of Modules needed






    Inverter DC window min - 250Vlot DC
    250Volt DC /  29.2Volt = 8.56Modules or 9 Modules Minimum

    Thursday, August 18, 2011

    12. Sizing the Battery Based System

    Performing Load Analysis
    Battery Bank capacity
    sizing inverter
    calculating required power output

    7.Batteries in Solar PV System

    Type of Batteries



    Factors affecting Battery capacity
    Temperature
    Cold battery - Chemical reaction will be slow and will not be efficient
    Hot Battery - Heat aids chemical process but the life of the battery will come down drastically.

    Batteries are like Human being the battery should keep in an ideal temp of 25"C like a person's comfortable temperature.Usually the battery will keep in a temperature controlled environment.

    Age
    As a battery ages, the chemical reactions won't work properly. The active material in the electrolyte will become layered in the plates of the battery

    Adding new battery in a battery bank may not be a good idea, old battery will drag the performance of the new one also.If the battery is new and well maintained, you can add a new battery to the bank.
    If you add an old battery in a new battery bank, the old one will affect the entire performance of the system.

    Discharge Rate of Battery

    Theoretical No of hrs a battery could work is the discharge rate of the bettery

    Eg 100Ah battery capacity means - 1Amp for 100Hrs (1 Amp X 100Hrs = 100Ah)before its completely discharged.
    *
    *
    *
    *
    *
    High voltage means high state of charge.

    A 100Ah battery will deliver 
    • More power delivered if 1Amp (will be more than 100Hrs)
    • Less power delivered if 100Amp (less than 1Hour)
    Usually battery manufacturers will specify C/20 rate 

    Specifying Batteries

    What is the right battery solution for the system?
    For Grid Interactive system - VRLA or sealed maintenance less battery will be  recommended, because the no of charging and deep discharging will be very less. 
    For Stand alone system - Flooded led-acid batteries will be specified, because that will last longer and will be deliver more energy in the environment.

    How Much my Client will maintain the system?
    If the client will not use the maintenance properly the VRLA will be recommended for both the systems.

    Specifying Battery Bank Size
    This is like buying fuel for one year for your car.
    You must think how much miles you drive and what will be the fuel consumption of the vehicle.

    Same as like we need to know - Electrical Load in the system we connected, No of Hour of Battery Backup

    A stand alone system - You need to measure all the loads
    A utility-interactive system (for Inverter and UPS) - only back up loads you need to consider

    Sizing the Charging source of the battery system
    If the Battery bank is too small compare to system, wont allow the system to charge fully
    If the Battery banks is big compare to the charging system, battery bank will not be fully charged, and will suffer in a long run.
    Sizing the right batter bank is like selecting the faucet and container for water.
    Considering other charging sources
    If the secondary source is utility grid, the charger in inverter will be too small, may take more time to charge the system.
    If the charging source another renewable energy source like micro wind turbine or micro hydro electric system that will take a lot of time to recharge the battery.
    If Secondary source is engine generator, recharging the battery bank is limited to size of generator.

    Days of Autonomy
    The number of days the the client want to go without needing his battery bank recharged.
    Eg.Two days Autonomy - will works without charging for two days.

    Try to optimize the capacity of battery bank based on the requirements.
    The Depth of discharge of the battery bank
    While you are sizing the battery bank you need to consider the DOD
    If you consider greater DOD, the battery bank size will be smaller, and lower cycles of charging/discharging
    If you consider lower DOD, the battery bank size will be bigger, and higher cycles of charging/discharging
    for many batteries you may consider the DOD as 50 to 75%
    Surveying no of strings
    If you have only one string, the electrons will pass through the same way and make sure that the batteries will charged and discharged in the same way.
    If you have more number of strings, properly maintain equal resistance in each path is difficult.
    Its better to reduce the number of strings or consider string monitor (will come with UPS and inverter) as an option.
    Examining Environmental conditions
    If the battery temp is less, the power delivered by the battery will be less than that of a normal battery.

    Temperature will play a role in the battery capacity, so its better to maintain the battery in a proper environment. also you may consider a temp sensor connected with the charge controller, this meter will measure the temperature and based on the feedback, the charge controller will deliver proper voltage and current.

    Wednesday, August 17, 2011

    8. Charge Controllers for Renewable Energy Applications

    A charge controller, or charge regulator is similar to the voltage regulator in your car. It regulates the voltage and current coming from the solar panels going to the battery. Most "12 volt" panels put out about 16 to 20 Volts, so if there is no regulation the batteries will be damaged from overcharging. Most batteries need around 14 to 14.5 volts to get fully charged.

    The Graphical representation of relationship between Battery voltage and time

    Bulk Charge
    First stage of charging
    Alow maximum flow of current by charge controller
    The process of charging the will continue up to voltage level reach up to "Bulk voltage set point"
    After "Bulk voltage set point". the current flow become less.
    Bulk voltage set point set by the battery manufacturer

    Absorption Charging

    Keep battery volatge constant
    Reduce the current sent to battery

    Float Charge
    minimum Battery voltage

    Features of Charge Controller
    Regulating the Charge
    Load control (were system directly connected to DC loads)
    Make sure that the battery will not be excessively drained - (will not alow the batery bank to drawin after a certain limit)
    DC lighting Loads - with load control facility
    Auxiliary load control - may be emergency disply in the bettery system, fan for the bettery bank
    Auxiliary fan needed to - bettery may produce hydrogen gas
    Warning light/Alarm -  for warning purpose
    Status Meter - Check the battery voltage

    Types of Charge Controllers
    • MPPT - Maximum Power Point Tracking Technology
    • PWM Technology (Pulse width Modulation)
    MPPT - Maximum Power Point Tracking Technology
    Mpp = V x I (refer IV Curve)
    Eg. For 12V Solkr Panel Mpp Voltage is 17Volt (Solar panels are designed to produce higher voltage than battery But when temperature rises voltage decreases.

    MPPT controller will take/tap power from solar panel (Regardless of battery voltage)

    PV Panel (17Volt produces) ---> Charge controller (13-15Volt)---->  Battery (12V)

    MPPT will regulate the voltage from 17 Volt to 13Volt and the current will increases Power remains the same

    Eg:
    PV Panels (Array in series) (150Volt produces) ---> Charge controller (13-15Volt)---->  Battery (12V)

    The Cost of MPPT is still remains High, Hence only used for larges arrays

    PWM Technology (Pulse width Modulation)
    Will regulate the voltage for the need of the battery

    PV Module ---->(17Volt)----> PWM ---->(14Volt)----> Battery 

    Disadvantage -
    The Current will be reduces hence the system will not be much Efficient
    In Absorption charging cycle, This charge in to it by pulsing the charge (turning the power On and Off)

    Used for kW Level projects from 0.5kW
    Used in small wind and Hydro projects

    Tuesday, August 16, 2011

    13. PV Solar System Wiring and Safety Devices

    Selection of Cable and Safety devices will play an important role in the budget of the system

    AC Voltage drop based on impedance
    DC Voltage drop based in resistance
    PV Cable Sizing
    Maximum current = No of modules (strings) wired in parallel  x the short circuit current Isc x 1.25

    OCPD Sizing
    Over Current Protection Device
    The Conductors are designed for 80% of capacity for 3Hr continuous rating.

    OCPD = 1.25 x 1.25 = 1.56-Multiplication factor'

    Nominal Voltage - Baseline of measuring Voltage - PV Modules will be availabel @ 12V & 24V modules

    Nominal Voltage   - 12Volt
    Operating Voltage - 17 to 18Volt




    Solar PV System Devices
    • Underground Feeder (UF)—may be used for interconnecting balance-of-systems (BOS) but not recommended for use within battery enclosures; single conductor UF wire may be used to interconnect modules in the array but this type of wire is not widely available.
    • Tray Cable (TC)—multi-conductor TC wire may be used for interconnecting BOS; TC has good resistance to sunlight but may not be marked as such.
    • Service Entrance (SE)—may be used for interconnecting BOS
    • Underground Service Entrance (USE)—may be used for interconnecting modules or BOS; may be used within battery enclosures
    • THHN—indicates wire with heat resistant thermoplastic sheathing; it may be used for interconnecting BOS but must be installed in conduit, either buried or above ground. It is resistant to moisture but should not be used in wet locations.
    • TW—refers to moisture resistant thermoplastic sheathing; it may be used for interconnecting BOS but must be installed in conduit. May be used in wet locations.

    5. Tracking System for PV System



    In photovoltaic tracking systems (heliostats), the surface of the module tracks the sun throughout the day. TheTracking can be along either one or two axes whereby tracking along two axes provides a higher power output. Compared to south-facing stationary systems, such a tracking system can increase the year’s total output by up to 30 % at 45° latitude. By setting tracking systems atop a mast one has the option of choosing the optimal site. No longer constricted to the disadvantages that come with surrounding Buildings, these systems have a 180° slewing range free of obstruction (i.e. shadows)


    Major components in a Tracking system - 
    • Motors
      • Sun sensors for the amount of light
      • Sun sensors for the shadows
      • Inclinometers for angles
      • Anemometer for wind speed
    • Sensors
      • Sun sensors for the amount of light
      • Sun sensors for the shadows
      • Inclinometers for angles
      • Anemometer for wind speed
    Types of tracking system - 
    • Timer Method
      • Place the array south east and let the pv moves according to the expected route
      • This method is inexpensive and misses a lot of light, inaccurate, lower energy output
    • Sun Sensor only
      • Array continually search for strongest light
      • This is inexpensive logic but uses energy to search the light.
    • Closed loop manual entry
      • Input Logic and Lattitude
      • High level of precision, clouds and shadows effect light inout
    Pros - 
    • More Energy efficiency
    • Maximum Utilization of power
    Cons - 
    • Maintenance
    • Initial cost
    • Reliability - Chances of failure of mechanical system 
    Application - 
    • Pumping system

    VI Characteristic of PV Module

    Vmp - Maximum Power Voltage
    Vmp is proportional to temperature

    Voltage Temperature Coeff.

    Every increase in temperature will affect the voltage in the module
    Ideally the modules should have low temp. coff.


    Crystalline - Mono Crystalline and Multi Crystalline have similar temp coeff.
    Thin film - less temp coefficient - ideally for high temperature applications

    Power Tolerence - Normal power tolerrence is 0% to 3%
    Eg 100W Module will produce 100W to 103W
    * But we must consider the system loss also

    Series fuse rating
    fuse rating 10A, 15A (up to 20A)

    Testing labs for PV module UL

    Standard - UL 1703 (for both mechanical and electrical)
    Mechanical Characteristics can be taken from the specification sheet.

    Standard Test conditions  (STC)
    Cell temp - 25"C / 77"F
    Irradiance - 1000W/SqM
    Air Mass - 1.5(AM 1.5)

    Normal conditions of installation
    Cell Temp - 75"C
    Standard Irradiance - 0 to 1250W/SqM
    From Technical specification sheet we need to take the Voc and Vmp


    Typical value for Mono- and Multi-Crystalline module is
                     Voc   -    -0.35% / C"
                     Vmp  -    -0.5% / C"

    -Ve means Negative temp coefficient, If temperature increases voltage decreses.

     Difference in temperature =  Cell temperature - STC
                                            =   15'C - 25"C
                                            =    -10"C
    Difference in temperature x Voltage Temp Coff.= % Change in Voltage
                 -10"C  x -0.35'C   =   3.5% Change in Voc
                 -10"C  x -0.5'C     =   5% Change in Vmp

    Irradiance comparison with irradiance sensor (pyronometer)
    Get the irradiance value using irradiance meter
    Eg measured value - 650W/Sqm (this may vary from 200 to 1250)
    STC of the cell is 1000W/Sqm
              650W//Sqm     =  0.65 - means 65% of the current should produce by the module
              1000W/Sqm
    *
     *
     *IV Curve of the module
    *
    *
    *


    Amount of current increases with temp is less so no need to consider this factor

    IV curve with varying irradiance

    Designer don't need to consider the irradiance on current, when designing the system

    Monday, August 15, 2011

    6. PV Modules

    Technical Terms related to PV Modules
    Isc
    Short circuit current - will be considered to size the conductor

    Imp
    Maximum Power current - or the maximum current produced by the PV module
    varies based on intensity of the sunlight striking on the module

    Voc
    Open circuit voltage - need to determine the maximum system voltage - voltage value in the absence of current value - while connecting in parallel this voltage will be considered

    Vmp
    Maximum Power Voltage - This voltage drops while the temperature increases - Operating voltage of the cell, this value is related to the current value of the 

    Mpp
    Max power point ( Vmp x Imp)
    Used to size the system


    Change in Voltage based on temperature
    Change in Current based on Irradiance

    Solar PV Cell Production

    Solar Cell is bacically a semi-conductor  *  In presence of Solar light that will become a conductor

    Silicon is the major element used for manufacturing the Solar PV Cell. Silicon is basically an insulator. while manufacturing the cells, silicon gas goes through the doping process.Boron and Phosphorous used in dopping process.

    Boron introduces in the first process,Phosphorous induces to manufacturing cell

    Negative - Phosphorous - Extra Electrons

    Positive   - Boron           - Extra Holes
    *
    *
    *
    *
                  Types of Modules
         ___________________I________________
              I                                             I                                     I
    Crystalline                          Hetero-Junction                      Thin Film
              I                                                                                   l
    Mono crystalline                                                                                 Amorphous core
    Multi Crystalline                                                                 Cadmium Telluride


    Crystalline
    Most commonly used type of module
    More Efficiency from 11 to 14W/SqFt.



    Mono crystalline
    Uniform molecular structure
    More Efficient
    Multi Crystalline 
    Many structure
    Less Efficient


    Irradiance - Intensity of radiation striking the earth considered in W/Sqm or kW/Sqm

    Power per Unit area will be depends on:-
    • Location of module related to sun
    • Time of the year
    • weather condition
    Edge of Cloud Effect
    Cloud pass over PV Array and prevents the sun from striking the array

    W/Sqm and time curve
    *
    *
    *


    • The Solar PV Modules are designed for constant output voltage and varying current, depends on the irradiance.
    • As soon as the ambient light will fall on the Module, the voltage is produced between the terminals.
    • Standard Test condition (STC) Irradiance value is 1000W/Sqm.
    • Pyronometer is used to measure the irradiance value.
    • Irradiance value will be indicated as kWH/Sqmtr.
    • PV Designer will calculate the value based on day month and year of irradiation

    Pyronometer
    Consider peak sun hour @ 4Hr
    850w/SqM x 4 Hrs = 3400W/SqM
    Dividing the value by one peak sun

                              3400W/SqM/Day        =   3.4Hrs/Day
                                1000w/SqM

    Reference Material
    Fundamental understanding of irradiance value based on location and time can be refer from NREL Website - "rredc.nrel.gov/solar/pubs/redbook"
    NREL Redbook